Table 13:Electrical data
ZS-06 through -12 standard motor - without powered convenience outlet
Size
(tons)
Volt
Compressors
(each)
OD fan
motors
(each)
Supply
blower
motor
Pwr exh
motor
Pwr
conv
outlet
Electric heat option
MCA
1
(amps)
MCA
1
with pwr
exh (amps)
Max fuse
2
/
breaker
3
size
(amps)
Max fuse
2
/
breaker
3
size with
pwr exh
(amps)
RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps
-06
(6)
208 11.2 84 18 2.1 5.2 5.5
None-- -34.640.145 50
E09 6.8 1 18.9 34.6 40.1 45 50
E18 13.5 2 37.5 53.4 60.3 60 70
E24 18 2 50 69 75.9 70 80
E36 25.5 2 70.8 95 101.9 100 110
230 11.2 84 18 2.1 5.2 5.5
None-- -34.640.145 50
E09 9 1 21.7 34.6 40.5 45 50
E18 18 2 43.3 60.6 67.5 70 70
E24 24 2 57.7 78.6 85.5 80 90
E36 34 2 81.8 108.8 115.6 110 125
460 5.6 44 9 1.26 2.6 2.2
None-- -17.719.920 25
E09 9 1 10.8 17.7 19.9 20 25
E18 18 2 21.7 30.4 33.1 35 35
E24 24 2 28.9 39.4 42.1 40 45
E36 34 2 40.9 54.4 57.1 60 60
575 3.8 34 6 0.66 2 1.8
None-- -11.913.715 15
E09 9 1 8.7 13.4 15.6 15 20
E18 18 2 17.3 24.1 26.4 25 30
E24 24 2 23.1 31.4 33.6 35 35
E36 34 2 32.7 43.4 45.6 45 50
-07
(7.5)
208 13.8 83.1 22 2.1 5.2 5.5
None-- -40.546 50 50
E09 6.8 1 18.9 40.5 46 50 50
E18 13.5 2 37.5 53.4 60.3 60 70
E24 18 2 50 69 75.9 70 80
E36 25.5 2 70.8 95 101.9 100 110
230 13.8 83.1 22 2.1 5.2 5.5
None-- -40.546 50 50
E09 9 1 21.7 40.5 46 50 50
E18 18 2 43.3 60.6 67.5 70 70
E24 24 2 57.7 78.6 85.5 80 90
E36 34 2 81.8 108.8 115.6 110 125
460 6.2 41 10 1.26 2.6 2.2
None-- -19.121.325 25
E09 9 1 10.8 19.1 21.3 25 25
E18 18 2 21.7 30.4 33.1 35 35
E24 24 2 28.9 39.4 42.1 40 45
E36 34 2 40.9 54.4 57.1 60 60
575 4.9 33 8 0.66 2 1.8
None-- -14.316.115 20
E09 9 1 8.7 14.3 16.1 15 20
E18 18 2 17.3 24.1 26.4 25 30
E24 24 2 23.1 31.4 33.6 35 35
E36 34 2 32.7 43.4 45.6 45 50
-08
(8.5)
208 14.5 98 23 3.03 6.8 5.5
None-- -45.551 60 60
E09 6.8 1 18.9 45.5 51 60 60
E18 13.5 2 37.5 55.4 62.3 60 70
E24 18 2 50 71 77.9 80 80
E36 25.5 2 70.8 97 103.9 100 110
230 14.5 98 23 3.03 6.8 5.5
None-- -45.551 60 60
E09 9 1 21.7 45.5 51 60 60
E18 18 2 43.3 62.6 69.5 70 70
E24 24 2 57.7 80.6 87.5 90 90
E36 34 2 81.8 110.8 117.6 125 125
460 6.3 55 10 1.6 3.4 2.2
None-- -20.823 25 25
E09 9 1 10.8 20.8 23 25 25
E18 18 2 21.7 31.4 34.1 35 35
E24 24 2 28.9 40.4 43.1 45 45
E36 34 2 40.9 55.4 58.1 60 60
575 6 41 9 1.35 2.4 1.8
None-- -18.620.420 25
E09 9 1 8.7 18.6 20.4 20 25
E18 18 2 17.3 24.6 26.9 25 30
E24 24 2 23.1 31.9 34.1 35 35
E36 34 2 32.7 43.9 46.1 45 50

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls ZST06 and is the answer not in the manual?

Johnson Controls ZST06 Specifications

General IconGeneral
BrandJohnson Controls
ModelZST06
CategoryAir Conditioner
LanguageEnglish

Related product manuals