JP FLUID CONTROL
AG-5 series
Electric actuator
1
AG-5 series actuator www.jpfluidcontrol.com
Model
AG-550-A
AG-550-B
Response time
13s
13s
Voltage
100-230V AC ±10%
24 AC/DC ±10% (AC/DC automatically
detected)
Utility frequency
50/60Hz
50/60Hz
Torque (Max.)
50Nm
50Nm
Current (Max.)
0.45A
1.2A
Current (Nom.)
0.13A
0.25A
Resolution
0.6°
0.6°
Housing material
Powder coated aluminum
Powder coated aluminum
Seal material
NBR
NBR
Ambient temperature range
-10°C to max. 50°C
-10°C to max. 50°C
ISO 5211 flange
F03, F05 and F07. 9, 10 and 12mm
thread depth respectively
F03, F05 and F07. 9, 10 and 12mm thread
depth respectively
Duty cycle
S2 30Min
Properties
14 x 14 Star connection
IP67 weather proof rating for housing
Manual override lever for safety-control
Cable entry: 2 x ½” PF
Two auxiliary limit switches for position feedback
1W space heater
101,6 x 120,6 x 128,6 mm L x W x H
Torque 50Nm
Open/Close 13s
ISO 5211 F03/F05/F07
Manual override
Position indicator
Position feedback
The AG-series is a range of
high-quality quarterturn actuators
to control the position of valves
with an ISO 5211 flange of type
F03, F05 and F07. The actuator
can deliver 50Nm in a fast and
smooth operation. The dome
indicator provides a clear visual
inspection of the valve position.
The actuator features a manual
override and 2 auxiliary limit
switches for position feedback.
Question and Answer IconNeed help?

Do you have a question about the JP AG Series and is the answer not in the manual?

JP AG Series Specifications

General IconGeneral
BrandJP
ModelAG Series
CategoryController
LanguageEnglish

Summary

Safety Instructions

General Safety Instructions

Read safety instructions carefully before installation, use or maintenance.

Compliance

Actuators are CE marked and comply with LVD and EMC Directives.

Intended Use

Suitable for rotary valves requiring quarter-turn operation.

Duty Cycle

Continuous use for 30 minutes (S2 30 min) requires cooldown.

Identification

Components

Working Conditions

Step-by-step Installation Guide

Installation Safety Precautions

Disconnect electricity and avoid sharp objects before starting installation.

Electrical Wiring

Grounding Electrical Equipment

Never use piping for grounding; connect ground to terminal 1.

Feedback

Feedback Circuit Precautions

Apply load (max. 5A) and correct polarity in feedback circuit.

Mounting

Actuator and Valve Alignment

Align actuator and valve in open or closed position for correct indicator.

Mounting to ISO 5211 Flanges

Mount actuator to valves with ISO 5211 flange F03, F05, or F07.

Actuator Setting and Configuration

Manual Override Operation

Disconnect power before using manual override; shift lever and rotate wheel.

Re-coupling Gears to Motor

Shift lever to 'auto' and wiggle wheel to re-couple gears after manual operation.

Limit Switch Adjustment

Cam Adjustment Range

Limit switch cams adjustable within a limited range of less than 10 degrees.