Installation Instructions Powador 1501xi/2501xi*/3501xi/4501xi/5001xi**_EN Page 9
Section 4 · Technical Data
Country-specifi c setting of parameters
Parameter
Country
Line voltage
range
(in V)
Line voltage
in accordance
with EN 50160
(in V)
Standard fre-
quency
range
(in Hz)
Switch-on
value
(in seconds)
after a re-start
Operation
resumption
time
(in seconds) after
a fault
Germany
190....264 253 V 47.5 – 50.2 > 180 > 30
Spain
196....254
–
49.0 – 51.0
> 180 > 180
Italy
190....264
– 49.7 – 50.3 > 180 > 30
France
190....264 253 V 47.5 – 51.0 > 180 > 30
Greece
190....264
– 49.5 – 50.5 > 180 > 180
South Korea
194....242
– 59.3 – 60.5 > 360 > 360
Czech Republic
196....252 253 V 49.5 – 50.5 > 180 > 30
Portugal
196....264
– 47.0 – 51.0 > 180 > 30
UK
208....264
–
49.0 – 50.5 > 180 > 180
Australia
208....264
– 47.5 – 52.0 > 120 > 60