KANE425 manual Page 17
When stabilisation is complete press to start the tightness test:
TIGHTN’S
P1 20.01
Pressure at start of tightness test
P1 20.01
Real time pressure reading
TIME 119
Tightness default time is 2 minutes. Can
be changed via “Menu”.
When complete the display will show:
LOG 01
The tightness test is automatically stored in the
memory. The log number for the test is displayed.
P1 20.01
Pressure at start of tightness test
P2 19.98
Pressure at end of tightness test
PRINT
Ð
Press
to print the tightness test (also sends to PC if Bluetooth fitted).
Viewing / printing a logged tightness test
Select MENU / REPORT / TIGHTN’S / VIEW
Use
or to select the log number to be viewed / printed.
Press
to print the test (also sends to PC if Bluetooth fitted).