When complete press to start the tightness test:
TIGHTN’S
P1 20.01
Pressure at start of tightness test.
P2 20.01
Real time pressure reading.
TIME 119
Tightness default time is 2 minutes. Can be
changed via “Menu”.
When complete the display will show:
LOG 01
The tightness test is automatically stored in
the memory.
P1 20.01
Pressure at start of tightness test.
P2 19.98
Pressure at end of tightness test.
PRINT Ð
Press to print the complete test.
Viewing / printing a logged Let-by and Tightness test
Select MENU / REPORT / TIGHTN’S / VIEW
Use
or to select the log number to be printed.
Press
/ to print the test, (or send to PC via optional Bluetooth).
Note:
The analysers’s memory can store up to 20 tightness tests. Tightness tests are
logged automatically therefore the tightness section of the memory will be full after the
20
th
tightness test is complete. Before the 21
st
tightness test can be performed the
tightness section of the memory must be cleared. To do this select MENU / REPORT
/ TIGHTN’S / DEL ALL / YES then press
.