4.3 LET-BY & TIGHTNESS TESTING
Select “Tightness”. The pump stops automatically. Press / to auto-
zero the pressure sensor. Connect from the test point to P1 using a black connector
and manometer hose.
The display shows “LET BY?”. Use
, and to select YES or NO.
If YES is selected set the let-by pressure then press
to start the let-by test. The
display shows:
LET BY
The let-by test is automatically stored in the
memory.
P1 10.15
Pressure at start of let-by test.
P2 10.15
Real time pressure reading.
TIME 59
Let-by default time is 1 minute. Can be
changed via “Menu”.
If the let-by test fails simply move the rotary switch to any position other than
“tightness” to abort the test.
If the let-by test passes adjust the gas pressure for the tightness test and press
to
start the stabilisation test. The display shows:
STABIL’N
P1 20.01
Real time pressure reading.
mbar
Pressure units.
TIME 59
Stabilisation default time is 1 minute. Can be
changed via “Menu”.