EasyManuals Logo

KB Genesis KBAC-24D User Manual

KB Genesis KBAC-24D
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
A B C D E
10
Description Specification Factory Setting
115 Volt AC Line Input Voltage Operating Range (Volts AC) 115 (±15%)
208/230 Volt AC Line Input Voltage Operating Range (Volts AC) 208 (-15%) / 230 (+15%)
400/460 Volt AC Line Input Voltage Operating Range (Volts AC) 380 (-15%) – 460 (+15%)
Maximum Load (% Current Overload for 2 Minutes) 150
Carrier, Switching Frequency (kHz) 16, 8
Signal Following Input Voltage Range
1
(Volts DC)
0 – 5
Output Frequency Resolution (Bits, Hz) 10, .06
Minimum Speed Trimpot (MIN) Range (% Frequency Setting) 0 – 40 0
Maximum Speed Trimpot (MAX) Range (% Frequency Setting) 70 – 110 100
Acceleration Trimpot (ACCEL) and Deceleration Trimpot (DECEL) Range (Seconds) .3 – 20 1.5
Boost Trimpot (BOOST) Range (Volts/Hz) 0 – 30 5
Slip Compensation Trimpot (COMP) Range at Drive Rating (Volts/Hz) 0 – 3 1.5
Current Limit Trimpot (CL) Range (% Full Load) 40 – 200 160
Jog Trimpot (JOG) Range (% Frequency Setting) 0 – 100 35
Motor Frequency Setting (Hz) (Jumper J5) 50, 60 60
Output Frequency Multiplier (1X, 2X) (Jumper J4)
2
1, 2 1
Minimum Operating Frequency at Motor (Hz) 1
Speed Range (Ratio) 60:1
Speed Regulation (30:1 Speed Range, 0 – Full Load) (% Base Speed)
3
2.5
Overload Protector Trip Time for Stalled Motor (Seconds) 6
Undervoltage/Overvoltage Trip Points for 115 Volt AC Line Input 5%) (Volts AC)
4
76 – 141
Undervoltage/Overvoltage Trip Points for 208/230 Volt AC Line Input 5%) (Volts AC)
4
151 – 282
Undervoltage/Overvoltage Trip Points for 400/460 Volt AC Line Input 5%) (Volts AC)
4
302 – 567
Run/Fault Relay Output Contact Rating (Amps at 30 Volts DC, 125 Volts AC, 250 Volts AC) 1, 0.5, 0.25
Operating Temperature Range (°C / °F) 0 – 45 / 32 – 113
TABLE 3 – GENERAL PERFORMANCE SPECIFICATIONS
TABLE 4 – ELECTRICAL RATINGS
Notes: 1. Requires an isolated signal. If a non-isolated signal is used, or if using 0 to ±2.5 thru 0 to ±25 Volts DC, or 4 – 20 mA DC signal input,
install the SIAC Signal Isolator (Part No. 9600). 2. Allows the motor to operate up to two times the rated RPM. Constant horsepower will result when
operating the drive in the “X2” mode above the motor rated frequency. 3. Dependent on motor performance. 4. Do not operate the drive outside the
specified AC line input voltage operating range.
Model No.
Part No.
AC Line Input
Fuse or
Circuit
Breaker
Rating
(Amps)
Drive Output
Motor Horsepower
Selection
2
(Jumper J2)
Net Wt.
Volts AC
(50/60 Hz)
Phase
(φ)
Maximum
Current
(Amps AC)
Voltage
Range
(Nominal)
(Volts AC)
Maximum
Continuous
Load Current
(RMS Amps/Phase)
Maximum
Horsepower
(HP (kW))Black
White
1
lbs kg
KBAC-24D 9987 9988
115 1 16 20 0 – 230
3.6 1 (.75) 1 3/4 1/2 1/4 1/8 5.9 2.7
208/230 1 10 15 0 – 230
KBAC-27D 9520 9521
115 1 22 25 0 – 230 5.5 1
1
2 (1.13)
1
1
2
4
1 3/4 1/2 10.3 4.7
208/230 1 15 20 0 – 230 6.7 2 (1.5)
2
4
KBAC-29 9528 9529 208/230
1 15 20 0 – 230 6.7 2 (1.5)
2
5
1
1
2 1 3/4 10.3 4.7
3 10.8 15 0 230 9.0 3 (2.25)
3
5
KBAC-45
3
9530 9531 400/460 3 5.3 10 0 – 400/460 4.6 3 (2.25) 3 2 1
1
2 1 3/4 10.3 4.7
KBAC-48
3
9540 9541 400/460 3 9.6 10 0 – 400/460 8.3 5 (3.75) 5 3 2 1
1
2 1 10.3 4.7
Notes: 1. White FDA approved finish. 2. Bold indicates factory setting. Jumper J2 on Model KBAC-24D is labeled “1”, “3/4”, “1/2”, “1/4”, “1/8” (facto-
ry set to the “1” position). Jumper J2 on Model KBAC-27D is labeled “2”, “1
1
2”, “1”, “3/4”, “1/2” (factory set to the “1
1
2 position). Jumper J2 on
Models KBAC-29, 45, 48 is labeled “A”, “B”, “C”, “D”, “E” (factory set according to the table). 3. Models KBAC-45, 48 are rated 0 400 Volts AC for
50 Hz motor operation and 0 – 460 Volts AC for 60 Hz motor operation. 4. Model KBAC-27D is rated 1
1
2 HP maximum with 115 Volt AC line input and
2 HP maximum with 208/230 Volt AC line input. 5. Model KBAC-29 is rated 2 HP maximum with single-phase AC line input and 3 HP maximum with