EasyManua.ls Logo

KBR F144-MS-1V1C1TI6DO-3 - Hardware Inputs and Outputs; 11.7.1 Hardware Inputs; 11.7.2 Hardware Outputs

KBR F144-MS-1V1C1TI6DO-3
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rev. 1.00
22585_EDEBDA0252-0318-1_EN
48
KBR multicomp F144-3 6DO/12DO Technical data
11.7 Hardware inputs and outputs
11.7.1 Hardware inputs
Voltage
measuring
input
U
PH-NPH-N
or U
PH-PH
30 - 690 VAC (max. permissible value: 790
VAC)
Input impedance 750 kOhm
Measuring range 1 measuring range,
measuring voltage transformer is congu-
rable
Current
measuring
input
I
L1
or I
L2
or I
L3
0.015 - 5 A (max. permissible value: 6 A)
Power consumption 0.3 VA at 6 A, 0.05 VA at 1.2 A
Measuring range 1 measuring range,
current transformer is congurable
Analog input PT 1000 measurement
sensor
Temperature measurement -10 °C to 60 °C,
+/- 2 °C
max. cable length < 3 meters
11.7.2 Hardware outputs
Alarm relay Switching capacity 250 V (AC) / 2 A oating
Optocoupler
output
Switching capacity approx. 5 to 30 VDC, max. 35mA,
external supply
Serial interface BUS RS485 for connection to the Modbus
Protocol, baud rate Modbus RTU,
bud rate 4800, 9600, 19200, 38400
Parity none, even, odd
Addressing Modbus:
manual setting on the device, address 1 to
247