Rev. 1.00
22585_EDEBDA0252-0318-1_EN
49
KBR multicomp F144-3 6DO/12DOTechnical data
11.8 Electrical connection
Connection elements Plug-in terminals
Permissible cross-section
of the connection lines
2.5 mm
2
Measurement
voltage inputs
Fuse protection max. 6 A
Measuring
current input
Fuse protection NONE!!! Always short-circuit current trans-
former terminals k and l before opening the
circuit!
Input control
voltage
Fuse protection max. 6 A
BUS
connection
Connection material To ensure proper operation, only use
shielded twisted-pair cables; e.g. I-Y(St)Y EIB
2x2x0.8
Relay output Fuse protection max 2 A medium time-lag
Transformer
connection
Connections See wiring diagram
Interface
connection
Pins for BUS connec-
tion via RS-485
Terminal 90
Terminal 91 A
Terminal 92 B