GB - 11
3.3.3 Mains connection
Mains connection 230 V 1-phase Mains connection 230 V 3-phase
1 x 180…260 Vac
++
--
W
T1
L1
PE
N

U
PB
V
W
L1
N/L2
L3
T2
PE
3 x 180…260 Vac
U
T1
T2
W
V
L1
PE

L2
L3
++
--
L3
L1
PE
N/L2
PB
Protection Mains connection 400 V 3-phase
Fuse (see chapter 2.3) or
power protective switch
at DC-supply pay attention to the per-
missible voltage range of the fuses
3 x 305…528 Vac
U
PB
T1
T2
W
V
L1
PE

L2
L3
++
--
L3
L2
L1
PE
DC-connection 230 V-class DC-connection 400 V-class
250…370 Vdc
U
PB
T1
T2
N/L2
V

-
+
++
--
L3
W
L1
PE
420…720 Vdc
U
PB
T1
T2
L2
V

-
+
++
--
L3
W
L1
PE
This product can cause a d.c. current in the protective conductor. Where a
residual current device (RCD) is used for protection in case of direct or indirect
contact, only an RCD of Type B is allowed on the supply side of this product.
Otherwise, another protective measure shall be applied, such as separation
from the environment by double or reinforced insulation, or isolation from the
supply system by a transformator.
Installation and Connection

Table of Contents

Other manuals for KEB ACOMBIVERT F5 X3A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB ACOMBIVERT F5 X3A and is the answer not in the manual?

KEB ACOMBIVERT F5 X3A Specifications

General IconGeneral
BrandKEB
ModelACOMBIVERT F5 X3A
CategoryDC Drives
LanguageEnglish

Related product manuals