Display Value Description
E.buS 18 Error, bus, failure in serial communication
E.dOH 9 Error, drive-overheat, motor overheats and prewarning time has run out
E.dSP 51 Error, digital signal processor, error in signal processor
E.PrF 46 Error, prohibited rotation forward, error in the software limit switch (when the set
direction of rotation is forward, the software limit switch for forward is inactive)
E.Prr 47 Error, prohibited rotation reverse, error in the software limit switch (when the set
direction of rotation is reverse, the software limit switch for reverse is inactive)
E.hyb 52 Error, hybrid, error in the encoder input card
E.EnC 32 Error, encoder, error in the encoder break
(reset only possible with Power-On-Reset)
E.LSF 15 Error, load shunt fault
E.OC 4 Error, overcurrent, overcurrent short-time peak overloading
E.OH 8 Error, overheated, overheating of the inverter
E.OH2 30 Error, overheat 2, electronic motor protection
E.nOH 36 Error, no overheat, overheating no longer preset, can be reset (valid for malfunction
E.OH or E.OH2)
E.OL 16 Error, overload, continuous overload, for cooling down the inverter has to stay
supplied with power, the cooling time depends on the previous overload time
E.OL2 53 Error overload, overloading of the inverter at output frequency < 3 Hz
E.nOL 17 Error, no overload, cooling time has run out, error can be reset
E.OP 1 Error, overpotential, overvoltage in the DC voltage circuit
E.OS 105 Error, overspeed, overspeed (can only be reset with power-on-reset
E.PuC 49 Error, power unit code, invalid power circuit recognition
E.SEt 39 Error, set, set selection error, check LF.02
E.UP 2 Error, underpotential, undervoltage im DC voltage circuit