4 Connections and wiring
4.1 Power supply
WARNING!
Danger of personal injury due to electric shock!
Supply the device exclusively from power sources that have an extra low
voltage (e.g. SELV or PELV according to EN 61131-2)
Connect only voltages and power circuits to connections, terminals and
interfaces up to 50 V rated voltage that have a secure disconnect for haz-
ardous voltages (e.g. with sufficient isolation).
CAUTION!
Fire hazard during module failure!
Provide suitable fuses for the 24 V DC power supply for the final application.
Only fuses with a maximum nominal disconnecting current of 10 A may be
used.
4.1.1 Module supply
The module is supplied by the CPU via the K-Bus. The max. permitted fuse is
10A. (recommended fuse protection: circuit line breaker LSS 10A – type B).
4.1.2 Supply for connected transducers
CAUTION!
No galvanic isolation!
Voltage reversal leads to a short circuit between GND and 24 V.
The MM 240/A provides a 24 V and 5 V supply voltage for the connected in-
cremental encoders.
Power supply is via the 24 V terminal at the front. The 24 V are looped through
secured. In addition, 5 V are generated internally from the 24 V. The 5 V trans-
ducer supply can carry loads of up to 100 mA each.
4.2 Latch inputs
The latch inputs can be operated in 2 operating modes:
as SINK input,
as SOURCE input.
The configuration is carried out by software.
MM 240/A
Connections and wiring
© KEBA 2010
Project engineering manual V1.08 13