K30-KLPD-PDI-4
14/10/20
- 4 -
SELECTION DATA - LOW TEMP. MODELS
KLP - LOW PROFILE EVAPORATORS
R407AR407A
R448AR448A
R449AR449A
Low Temperature - 6 FPI Models
Model
KLP
Qty.
Fans
Evaporator Temperature
Selection Capacity BTU/h
Air Flow
Refrig. Charge
R407AR407A
**
0°F
(-18°C)
-10°F
(-23°C)
-20°F
(-29°C)
-30°F
(-34°C)
-40°F
(-40°C)
CFM L/S LB. KG
104L
1
4310 4190 4070 3740 3460 750 350 0.7 0.3
105L 5190 5050 4900 4510 4170 705 330 1.1 0.5
106L 6710 6520 6330 5820 5380 680 320 1.5 0.7
207L
2
7590 7370 7160 6590 6090 1500 710 1.3 0.6
209L 9950 9670 9390 8640 7980 1410 670 1.4 0.6
211L 11980 11600 11300 10400 9610 1360 640 2.0 0.9
314L
3
14730 14300 13900 12800 11800 2115 1000 3.0 1.4
316L 17170 16700 16200 14900 13800 2040 960 4.0 1.8
418L
4
19500 19000 18400 16900 15600 2820 1330 3.3 1.5
421L 22470 21800 21200 19500 18000 2720 1280 3.9 1.8
526L 5 27670 26900
26100 24000 22200 3400 1600 6.5 2.9
631L 6 32970 32000 31100 28600 26400 4080 1930 7.8 3.5
- Capacities at other TD within a range of 8 to 15 °F (4.4 to 8.3°C) are directly proportional to TD, or use formula:
Capacity = Rated capacity ÷ 10 x TD.
** For R448A/R449A, use conversion factor 0.96
R404A
R507
Low Temperature - 6 FPI Models
Model
KLP
Qty.
Fans
Evaporator Temperature
Selection Capacity BTU/h
Air Flow
Refrig. Charge
R404A
R507
0°F
(-18°C)
-10°F
(-23°C)
-20°F
(-29°C)
-30°F
(-34°C)
-40°F
(-40°C)
CFM L/S LB. KG
104L
1
4210 4090 3970 3650 3370 750 350 0.6 0.3
105L 5070 4920 4780 4400 4060 705 330 1.0 0.5
106L 6540 6360 6170 5680 5240 680 320 1.4 0.6
207L
2
7400 7190 6980 6420 5930 1500 710 1.2 0.5
209L 9710 9430 9160 8430 7790 1410 670 1.3 0.6
211L 11660 11330 11000 10120 9350 1360 640 1.8 0.8
314L
3
14420 14000 13600 12500 11560 2115 1000 2.8 1.3
316L 16750 16300 15800 14500 13430 2040 960 3.7 1.7
418L
4
18970 18400 17900 16500 15220 2820 1330 3.0 1.4
421L 21840 21200 20600 19000 17510 2720 1280 3.6 1.6
526L 5 27140
26400 25600 23600 21760 3400 1600 6.0 2.7
631L 6 32220 31300 30400 28000 25840 4080 1930 7.2 3.3
Theabovecapacitieswereratedbasedonnominal10℉TD
Capacities at other TD within a range of 8 to 15 °F (4.4 to 8.3°C) are directly proportional to TD, or use formula:
Capacity = Rated capacity ÷ 10 x TD.