K30-KLPD-PDI-4
14/10/20
- 5 -
SELECTION DATA - LOW TEMP. MODELS
KLP - LOW PROFILE EVAPORATORS
R407AR407A
R448AR448A
R449AR449A
Low Temperature - 4 FPI Models
Model
KLP
Qty.
Fans
Evaporator Temperature
Selection Capacity BTU/h
Air Flow
Refrig. Charge
R407AR407A
**
0°F
(-18°C)
-10°F
(-23°C)
-20°F
(-29°C)
-30°F
(-34°C)
-40°F
(-40°C)
CFM L/S LB. KG
103V
1
3880 3770 3660 3370 3110 750 350 0.7 0.3
104V 4610 4480 4350 4000 3700 705 330 1.1 0.5
106V 5880 5720 5550 5110 4720 680 320 1.5 0.7
207V
2
7070 6870 6670 6140 5670 1500 710 1.3 0.6
208V 8590 8340 8100 7450 6890 1410 670 1.4 0.6
211V 11200 10900 10600 9750 9010 1360 640 2.0 0.9
313V
3
13400 13000 12600 11600 10700 2115 1000 3.0 1.4
316V 16500 16100 15600 14400 13300 2040 960 4.0 1.8
418V
4
18800 18200 17700 16300 15000 2820 1330 3.3 1.5
421V 22300 21600 21000 19300 17900 2720 1280 3.9 1.8
524V 5 25300 24600
23900 22000 20300 3400 1600 6.5 2.9
627V 6 28400 27600 26800 24700 22800 4080 1930 7.8 3.5
- Capacities at other TD within a range of 8 to 15 °F (4.4 to 8.3°C) are directly proportional to TD, or use formula:
Capacity = Rated capacity ÷ 10 x TD.
** For R448A/R449A, use conversion factor 0.96
R404A
R507
Low Temperature - 4 FPI Models
Model
KLP
Qty.
Fans
Evaporator Temperature
Selection Capacity BTU/h
Air Flow
Refrig. Charge
R404A
R507
0°F
(-18°C)
-10°F
(-23°C)
-20°F
(-29°C)
-30°F
(-34°C)
-40°F
(-40°C)
CFM L/S LB. KG
103V
1
3640 3530 3430 3160 2920 750 350 0.6 0.3
104V 4300 4180 4060 3740 3450 705 330 1.0 0.5
106V 5500 5350 5190 4770 4410 680 320 1.4 0.6
207V
2
6600 6420 6230 5730 5300 1500 710 1.2 0.5
208V 8020 7800 7570 6960 6430 1410 670 1.3 0.6
211V 10460 10170 9870 9080 8390 1360 640 1.8 0.8
313V
3
12400 12100 11700 10760 9950 2115 1000 2.8 1.3
316V 15370 14900 14500 13300 12330 2040 960 3.7 1.7
418V
4
17600 17100 16600 15300 14110 2820 1330 3.0 1.4
421V 20880 20300 19700 18100 16750 2720 1280 3.6 1.6
524V 5 23640
23000 22300 20500 18960 3400 1600 6.0 2.7
627V 6 26610 25900 25100 23100 21340 4080 1930 7.2 3.3
Theabovecapacitieswereratedbasedonnominal10℉TD
Capacities at other TD within a range of 8 to 15 °F (4.4 to 8.3°C) are directly proportional to TD, or use formula:
Capacity = Rated capacity ÷ 10 x TD.