Program Feature or Option Permitted in UL 864
? (Y / N)
Possible Settings Settings Permitted
In UL 864
Remove AUX 24V
On Fire Alarm
Code: 28
Y Set / Clear Set / Clear
Set Z1-Z8, Zone Alarm Delayed
Code: 31 - 38
N Set / Clear for each
zone
Clear all zones
Set Z1-Z8, Zone Alarm From
Detector Verified
Code: 41 - 48
Y Set / Clear for each
zone
Set / Clear for each
zone
Set Z1-Z8, Coincidence Zone
Code: 51 - 58
Y Set / Clear for each
zone
Set / Clear for each
zone
Set Z1-Z8, Configure Zone
I.S. Barrier
Code: 61 - 68
N Set / Clear for each
zone
Clear all zones
Set Z1-Z8, Zone Short Circuit
Triggers Alarm
Code: 71 - 78
Y Set / Clear for each
zone
Set / Clear for each
zone
Set Z1-Z8, Zone Non-Latching
Code: 81 88
(2)
Y Set / Clear for each
zone
Reference note
(2)
Set Z1-Z8, Zone Alarm
Generates Supervisory
Code: 91 98
(3)
Y Set / Clear for each
zone
Reference note
(3)
Set Z1-Z8, Alarm must be
present for 30 seconds
Code: A1 - A8
Y Set / Clear for each
zone
Set / Clear for each
zone
Set Z1-Z8, Zone Fire Relay
Deactivated
Code: E1 - E8
Y Set / Clear for each
zone
Set / Clear for each
zone
(2)
Zones configured for reporting supervisory conditions are permitted to be configured as non-latching or
latching. Zones configured for reporting fire conditions are permitted to be configured as latching only. Fire
zones shall not be configured as non-latching.
(3)
Zones configured for reporting supervisory conditions must
not contain smoke detectors or other devices intended for reporting fire conditions.