Installing the Transformer Fuse
To install the 6.3 Amp transformer fuse:
1 Confirm that 115 VAC or 230 VAC is turned-off at the source.
2 Install the replacement fuse in the fuse-housing.
3 Close the fascia-door of the Sigma A-CP Fire Control Panel.
4 Connect NAC Power and Power inserts on the fascia-terminal strip of the Sigma A-CP Fire Control Panel.
5 Connect the red-lead of the recharging circuit to the positive terminal of the standby-battery.
6 Secure the retaining-screw to the fascia-door and the cabinet of the Sigma A-CP Fire Control Panel.
7 Turn on 115 VAC or 230 VAC at the power source.
8 Test the fire control panel by operating it to determine that it functions.
AC Input Fuse
The following procedures describe methods for removing and installing the 5 AC input fuse of the
Sigma A-CP Fire Control Panel.
Removing the AC Input Fuse
To remove the 5 Amp AC input fuse:
1 Turn off 115 VAC or 230 VAC at the power source.
2 Disconnect the red-lead of the recharging circuit from the positive terminal of the standby-battery.
3 Remove NAC Power and Power inserts from the fascia terminal strip of the Sigma A-CP Fire Control Panel.
4 Remove the retaining-screw securing the fascia to the cabinet of the Sigma A-CP Fire Control Panel.
5 Open the fascia-door of the Sigma A-CP Fire Control Panel.
6 Remove the AC input fuse from the terminal block housing.