Notice to Users, Installers, Authorities Having Jurisdiction, and other involved parties.
This product incorporates field-programmable software. In order for the product to comply with the
requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 10th
Edition, certain programming features or options must be limited to specific values or not used at all
as indicated below.
Program Feature or Option Permitted in UL 864
? (Y / N)
Possible Settings Settings Permitted
In UL 864
Set Alarm Delay
(1)
Code: 00 to 09
Y 00 to 09 00 to 09
Set NAC Pattern
Code: 10 to 16
Y 10 to 16 10 to 16
Disable Fire Alarm Buzzer
Code: 21
Y
Set / Clear Set / Clear
Disable Trbl. Relay
Code: 22
Y Set / Clear Set / Clear
Disable Earth Trbl.
Code: 23
N Set / Clear Clear
Set Strobe Activation During
Alarm Silence
Code: 24
Y Set / Clear Set / Clear
Set Zone 1 Class A Operation
Code: 25
Y Set / Clear Set / Clear
Disable Fire Relay
Code: 26
Y Set / Clear Set / Clear
Remove AUX 24V
On Panel Reset
Code: C27
Y Set / Clear Set / Clear
(1)
This setting has no effect on options 31 through 38 when these options are set to clear.