UL Listing Requirement
All control panel designs restrict the number of NAC devices installed in circuits based on the rated
current threshold. Some control panel designs further restrict the number of NAC devices installed in
circuits based on device synchronization in addition to the rated current threshold. These control
panel designs can reduce the population of NAC devices below the number of devices that would be
considered for the rated current threshold.
NAC outputs of the Sigma A-CP Fire Control Panel are not limited by conditions other than the maximum rated
current threshold. NAC outputs of the Sigma A-CP Fire Control Panel can operate combinations of Kentec
authorized NAC devices as long as the total load of NAC 1 and NAC 2 does not exceed 4 A.
The following series of Gentex NAC devices are compatible for use on the special application outputs of
NAC 1 and NAC 2 when operating each NAC output below 2.5 A:
Name of Series Environment Model Series Description Mounting Type
WSSPK Series
Outdoor WSSPK24-15/75 Speaker Strobe Wall
SSPK24WLP Series
Indoor SSPK24WLP Speaker Strobe Wall
SSPKCLP Series
Indoor SSPK24CLP Speaker Strobe Ceiling
Commander4 Series
Indoor GCC24 Horn Strobe Ceiling
Commander4 Series
Indoor GCS24 Strobe Ceiling
Commander3 Series
Indoor GEC3-24 Horn Strobe Wall
Commander3 Series
Indoor GES3-24 Strobe Wall
Commander3 Series
Indoor GEH24 Horn Wall
Commander2 Series
Indoor GEC24 Horn Strobe Wall
Commander2 Series
Indoor GES24 Strobe Wall
Commander2 Series
Indoor GEH24 Horn Wall