EasyManuals Logo

Keyscan CA8500B Technical Instructions

Default Icon
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #117 background imageLoading...
Page #117 background image
Keyscan Inc. Technical Guide (PC109x - 04.15)
117
Appendix C WSSKP-1
Keypad
Appendix C reviews typical Keyscan WSSKP-1 keypad connections and keypad/reader combination
connections.
Table 22 Keypad Power Specifications
Reader
Power
Notes
WSSKP-1
No digital output.
12 VDC, 20 mA
Orange wire not connected.
WSSKP-1
Digital output
12 VDC, 530 mA
Orange wire connected.
Installation Notes on Keypads
Do not run keypad cables in same conduit with AC power or signal cables.
Keep keypad cables at a minimum distance of 12 inches or 30 centimetres from AC, computer data, telephone
data, or electric lock device cables.
Do not install keypads within 3.5 feet or 1.1 metres of computer CRTs.
Do not install readers in areas where broad spectrum EMI noise may be present. Devices such as motors,
pumps, generators, and AC switching relays can create EMI noise.
Important
Keypads made by other manufacturers may not have the necessary Wiegand interface. Hence, these
keypads will not operate in dual card and PIN modes; they will only operate in card/reader simulation.

Table of Contents

Other manuals for Keyscan CA8500B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Keyscan CA8500B and is the answer not in the manual?

Keyscan CA8500B Specifications

General IconGeneral
BrandKeyscan
ModelCA8500B
CategoryControl Unit
LanguageEnglish

Related product manuals