Chapter 3: Programming
GSA-REL Technical Reference Manual 39
Step 2: Add the abort and manual release switch circuits
Note: Enter the information exactly as shown to ensure that you program the
application according to the manufacturer’s specifications.
1. Click Configure, and then click Cabinets.
2. Select the SLIC connected to the GSA-REL, and then click Configure.
3. Click the Modules tab, and then set the Quantity box to 1.
4. Enter the following information:
First address
Device type: Monitor
Model: REL
Personality: (3) Active B
Message text: GSA-REL1 A001 and ABORT SW
Second address
Device type: Pull
Personality: (1) Alarm B
Message text: GSA-REL1 A002 and MAN RELEASE
5. Click Add.
Step 3: Add the two releasing circuits
1. Set the Quantity box to 1.
2. Enter the following information:
First address
Device type: Output
Model: REL
Personality: (16) Output B
Message text: GSA-REL1 A003 and RELEASE 1 & 2
Second address
Device type: Monitor
Personality: (0) None
Message text: GSA-REL1 A004 and NOT USED
3. Click Add.
Step 4: Add the two prerelease circuits
1. Set the Quantity box to 1.
2. Enter the following information: