Chapter 3: Programming
44 GSA-REL Technical Reference Manual
1. Click the Mapping tab, and then click Model.
2. Look for a string of at least six RELs marked with red backgrounds and
double-click the first REL in the string.
3. If the serial number displayed in the Module Properties dialog is not the same
as the serial number shown on the bar code attached to the GSA-REL, click
Close, and then double-click the next REL in the string.
4. If the serial numbers are the same:
Click Select Expected.
In the Module Selection dialog, select the row that has the REL with the
Monitor device type and marked GSA-REL1 A001 Abort SW, and then click
OK.
Click Close.
5. Select the next REL, and then click Select Expected.
In the Module Selection dialog, select the row that has the REL with the
Output device type and marked GSA-REL1 A003 Release 1 & 2, and then
click OK.
Click Close.
6. Select the next REL, and then click Select Expected.
In the Module Selection dialog, select the row that has the REL with the
Output device type and marked GSA-REL1 A005 Prerelease 1 & 2, and then
click OK.
Click Close.
Step 13: Send the reconciled data to the loop controller
Click the Controller tab, and then click Send Signature Data.
See “System testingon page 46 for instructions on checking your work and
testing your system.