Chapter 3: Programming
GSA-REL Technical Reference Manual 43
2nd Text 1: REL1_PREREL
2nd Text 2: CKT_ACTIVE
When a circuit is activated, the GSA-CT2 module activates a monitor event. The
corresponding event message identifies which circuit was activated. No further
programming is necessary.
Step 10: Create a drill prerelease response
Here, you create a response that activates the prerelease circuits when someone
presses the Drill switch.
Note: Create this response only if required. Pressing Drill will activate the
prerelease circuits, but pressing Drill a second time will not restore the
prerelease circuits. You must press Reset to silence the prerelease circuits.
1. Click Configure > Correlations.
2. Click the Devices tab, and then select the Show Pseudo Points check box.
3. Select the circuit labeled Drill (address 007).
4. Click the Responses tab, click the Response Type arrow, and then select
Active.
Caution: Do not include the releasing circuits (RELEASE 1 & 2) in this response.
5. Click Outputs, select the device labeled GSA-REL1 A005 PRERELEASE 1 &
2, and then click OK.
Step 11: Retrieve the loop data from the SLIC
1. Click Configure, and then click Cabinets.
2. Select the SLIC connected to the GSA-REL, and then click Configure.
3. Set the Communications Port setting for the COM port used to connect the
service computer to the control panel.
4. Click Retrieve Signature Data.
5. After the upload has finished, click OK.
Step 12: Reconcile the actual and expected data
Caution: Clicking Accept Actual enters the selected device into the database
with its current programmed parameters. This corrupts the database if you have
already entered the device.