Chapter 3: Smoke control system programming 
VM-1 Smoke Management Application Guide  45 
Name: FSCS STATUS LEDS - CORR 9 
Inputs: 
Monitor, SUPPLY_FAN_OFF_RELAY 
Outputs: 
Steady, Low, Both, SUPPLY_FAN_OFF_LED 
 
Name: FSCS STATUS LEDS - CORR 10 
Inputs: 
Trouble, SUPPLY_FAN_OFF_RELAY 
Outputs: 
Steady, Low, Both, SUPPLY_FAN_TRBL_LED 
Controlling fans and dampers 
manually 
The FSCS is required to provide switches for controlling 
fans and dampers manually. Typically, the switches are 
disabled until the FSCS has control of the smoke control 
system.  
The correlation inputs and outputs shown below can be 
used to create correlations that demonstrate how to 
program manual controls for a supply fan and supply 
damper. Refer to Figure 23 on page 38 and Figure 24 on 
page 39. 
Name: FSCS MANUAL CONTROLS - CORR 1 
Inputs: 
Startup 
Outputs: 
Disable, Low, Both, FSCS_SW/LED_STRIP_1 
Steady, Low, Both, SUPPLY_FAN_AUTO_SW_LED 
Steady, Low, Both, 
SUPPLY_DAMPER_AUTO_SW_LED 
 
Name: FSCS MANUAL CONTROLS - CORR 2 
Inputs: 
Alarm, <all smoke control smoke 
detectors> 
Outputs: 
Enable, Low, Both, FSCS_SW/LED_STRIP_1 
 
Name: FSCS MANUAL CONTROLS - CORR 3 
Inputs: 
Switch, SUPPLY_FAN_ON_SW 
Outputs: 
LEDOFF, High, Both, 
SUPPLY_FAN_AUTO_SW_LED 
STEADY, High, Both, SUPPLY_FAN_ON_SW_LED 
ON, Low, High, SUPPLY_FAN_ON_RELAY  
 
Name: FSCS MANUAL CONTROLS - CORR 4 
Inputs: 
Switch, SUPPLY_FAN_OFF_SW 
Outputs: 
LEDOFF, High, Both, 
SUPPLY_FAN_AUTO_SW_LED 
STEADY, High, Both, SUPPLY_FAN_OFF_SW_LED 
OFF, High, Both, SUPPLY_FAN_ON_RELAY  
ON, High, Both, SUPPLY_FAN_OFF_RELAY 
 
Name: FSCS MANUAL CONTROLS - CORR 5 
Inputs: 
Switch, SUPPLY_DAMPER_OPEN_SW 
Outputs: 
LEDOFF, High, Both, 
SUPPLY_DAMPER_AUTO_SW_LED 
STEADY, High, Both, 
SUPPLY_DAMPER_OPEN_SW_LED 
ON, High, Both, SUPPLY_DAMPER_OPEN_RELAY 
 
Name: FSCS MANUAL CONTROLS - CORR 6 
Inputs: 
Switch, SUPPLY_DAMPER_CLOSE_SW 
Outputs: 
LEDOFF, High, Both, 
SUPPLY_DAMPER_AUTO_SW_LED 
STEADY, High, Both, 
SUPPLY_DAMPER_CLOSE_SW_LED 
OFF, High, Both, SUPPLY_DAMPER_OPEN_RELAY 
ON, High, Both, SUPPLY_DAMPER_CLOSE_RELAY