Also, some chargers just have settings for broad battery types like; flooded, gel, agm or lithium. Before
using these chargers on your battery, please contact KiloVault technical support for guidance.
Note: If you cannot find a specific setting, remember to check the settings for guidance. Also, please don’t
hesitate to contact KiloVault technical support for help.
4.1 - Inverter/Charger Settings
Setting
Values:
Volts are per HLX+ in a single string.
Amps are per parallel string.
1200 - Battery Capacity
1200 Wh, 100 Ah
2400 - Battery Capacity
2400 Wh, 150 Ah
3600 - Battery Capacity
3600 Wh, 300 Ah
1200 - Max Charge Current
80 A
2400 - Max Charge Current
150 A
3600 - Max Charge Current
200 A
Absorb End Amps
2 A
Absorb Time (some controllers do not allow a
selection under 6 minutes, please contact
KiloVault for additional information)
2 minutes or less
Absorb Voltage
14 V
Battery Temperature Compensation
0 mV/°C
Battery Type
Lithium or Custom, whichever lets you set the
recommended settings
Bulk Voltage
14 V
Charge Cycle
2 stage no float
Default Battery Temperature
Warm
Equalization
Disabled
Float Voltage
13.6 - Normally the inverter/charger is set to
2-Stage-No-Float, but if it has to be set then
used this value
HBCO (High Battery Cut Out)
14.4 V
LBCO (Low Battery Cut Out)
12.25 V (or as close as it can be set)
LBCO Delay
5 seconds
LBCO Hysteresis
0.5 V