Set the inverter max bulk current so that when
it is added to the charge controller current,
together they add up to less than the max
charge current for your battery bank.
Recharge/Re-Bulk Volts (≈80% DoD)
1200 - Recommended Charge Current
50 A or less per HLX in Parallel
2400 - Recommended Charge Current
100 A or less per HLX in Parallel
3600 - Recommended Charge Current
200 A or less per HLX+ in Parallel
4.2 - Solar Charge Controller Settings
Values:
Volts are per battery in a single string
Amps are per string in parallel
Battery Temperature Compensation
Do not use a battery temperature sensor
with these batteries!
If the sensor or compensation value is required
for a charge controller or inverter charger to
work, set the battery temperature compensation
to 0mV/°C
Battery Temperature Compensation
Lithium or Custom, whichever lets you set the
recommended settings
Battery Voltage - Nominal
Bulk Termination Voltage (if applicable)
Float Voltage (set below the resting voltage of
the battery bank)
≈13.4 V or lower. Low enough to not trigger
float when the battery "relaxes" after charging
stops.