EasyManua.ls Logo

KiloVault HLX+ - Page 24

KiloVault HLX+
29 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Overcurrent Protection - Time delay until high
discharge triggers protection @ 210±5 A
≈20 Seconds
Overcurrent Protection - Time delay until high
discharge triggers protection @ 400±20 A
≈3.5 Seconds
Overcurrent Protection (Charging) Release
Method
Discharge battery for immediate release.
Wait 1 minute for auto-release.
Overcurrent Protection (Discharging) Release
Method
Charge battery for immediate release.
Wait 1 minute for auto-release.
Peak or Surge Discharge Current
500 A, less than 3 second
Rated Capacity
200 Ah
Recommended Charge Current
≤100 A
3600 HLX+
Specification
Value
Heater
192 W
Internal Resistance
≤20mΩ
Maximum Continuous Charge Current
150 A
Maximum Continuous Discharge Current
200 A
Overcharge Protection Release Method
Discharge below 3.60±0.05 V / cell
Overcharge Protection Trigger Voltage
3.75±0.03 V / cell
Overdischarge Protection Release Method
Charge above 2.80±0.10 V/ cell
Overdischarge Protection Trigger Voltage
2.50±0.05 V / cell
Overcurrent Protection - Time delay until high
charge current triggers protection @ 210±5 A
≈25 Seconds
Overcurrent Protection - Time delay until high
discharge triggers protection @ 210±5 A
≈20 Seconds
Overcurrent Protection - Time delay until high
discharge triggers protection @ 400±20 A
≈3.5 Seconds
Overcurrent Protection (Charging) Release
Method
Discharge battery for immediate release.
Wait 1 minute for auto-release.
Overcurrent Protection (Discharging) Release
Method
Charge battery for immediate release.
Wait 1 minute for auto-release.
Peak or Surge Discharge Current
500 A, less than 3 seconds
Rated Capacity
300 Ah
Recommended Charge Current
≤150 A
KiloVault
®
LLC • 330 Codman Hill Road, Boxborough, MA 01719 • +1 (888) 218-5924 • info@kilovault.com www.kilovault.com
Revision 1.0, 06/2021
Page 24 of 29