Chapter 7 List of Parameters
66
Input terminal
X6 function
selection
Input terminal
X7 function
selection
Terminal control
mode selection
0: 2-wire operating mode 1
1:2-wire operating mode 2
2: 3-wire operating mode 1
3: 3-wire operation mode 2
4: 2-wires operation mode 3
Max. frequency
of input pulse
0.1~100.0(Max.100k)
Only valid when X7 is defined as
pulse input.
Center point of
pulse setting
selection
0:No center point
1:Center point mode 1,the center
point is(A6.10)/2.It is positive when
frequency less than center point.
2:Center point mode 2.The center
point is (A6.10)/2.It is negative when
frequency less then center point.
Inputterminal’s
positiveandnegati
ve logic
Binary setting
0:Positive logic.Terminal Xi is
enabled if it is connected to
corresponding common terminal, and
disabled if it is disconnected.
1:Negative logic.Terminal Xi is
disabled if it is connected to
corresponding common terminal, and
enabled is it is disconnected.
Unit’s place of
LED:BIT0~BIT3.X1~X4
Ten’s place of
LED:BIT0~BIT2.X5~X8
Bi-direction
pen-collector
0:Running signal(RUN)
1:Frequency arriving signal(FAR)