EasyManua.ls Logo

Kiturami K1-28E - 5.8 Heating System Filling and Pressurizing

Default Icon
55 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28
ۣૐ ۞ইૐ઺Ҵ ೠҴ࢑সӏѺ ಿ૕҃৔మ
5.7 Preparing the Wall
▪Afterconsideringthelocationpositiontoensuringitislevel
bothhorizontallyandvertically.
▪PleaserefertothetemplatebeforeinstallingtheCombi
boiler.
•Attachthetemplateexactlytothelocationwhereyouwantto
installtheappliance.
•Drill12mm(0.47inch)4holesatthepositionoftemplate
bracketwhichisappropriateplaceforinstallingtheheater.
•Afterfouranchorboltsinsertedintheholes,mountthewall
bracket.
CAUTION
Theboilerisheavy.Alwayslifttheunitwithassistance.
Becarefulnottodroptheboilerwhileliftingorhandlingit
toavoidbodilyinjuryordamagetotheunit.
5.8 Heating System Filling and Pressurizing
▪Whenconnectingthespaceheatingsystem,followthese
guidelines:
-Tightentheconnectionvalveswithcaretoavoiddamage.
-Testtheboilerforproperspaceheatingowandinspectfor
leaks.
▪Allingpointconnectionislocatedonthebottomsideof
theboiler,rstopenthehandleitandthenwatercomes
intoheatingsidefromDHWside.Atthistime,installermust
conrmproperlypressureinheatingsidetoworking.
Afterthat,primaryinstallinghastodothisoften,sincemight
benotenoughlledwater.
▪Allingloopdoesn’tsuppliedwiththeboiler.
Then,ifyoursiteshouldbeinstalledallingloop,mustbe
installeditwithqualiedtechnicalperson.Also,shouldbe
followedthelocalcodes.
▪Thellingmethodadoptedmustbeinaccordancewith
allrelevantwatersupplyregulationsanduseapproved
equipment.
5.9 DHW System Filling
▪Closeallhotwaterdrawofftaps.
▪Openthecoldwaterinletcock.
▪Slowlyopeneachdrawofftapandclosethemonlywhen
clearwater,freeofbubbles,isvisible.
▪AllDHWcircuits,connections,ttings,etc.shouldbefully
inaccordancewithrelevantstandardsandwatersupply
regulations.
▪Theboiler’smaximumworkingmainspressureis10bars,
thereforeallpipework,connections,ttings,etc.,should
besuitableforpressuresinexcessof10bars.
Apressurereducingvalvemustbettedforpressuresin
excessof10bars.Themanufacturerofanyoutletttings,
suchasashowervalve,mayrequirealowermaximum
pressure.Thepressurereductionmusttakeaccountofall
ttingsconnectedtotheDHWsystem.
•Afxthewallbracketsecurelytothewall.
Makesurethatitislevelanditcansupporttheweightofthe
Combiboiler.

Related product manuals