DocumentNo.:KE-4025-06  11/50
8.KITZOptionalAccessories
ThefollowingarerecommendedstandardaccessoriesforKITZBSeriesactuators.
Forotheraccessories,pleasecontactKITZ.
Accessories&Code Specifications Remarks
LS
LS-F
AC:
DC:
AC:
DC:
10A/125V10A/250V10A/480V
0.8A/115V0.4A/230V
5A/125V5A/250V
0.8A/125V0.4A/250V
LimitSwitch
LS Weather-proof
LS-F Explosion-proof
Contactcircuit: 2-Circurtdoublebreak
For initiating electric signals to check open or
closepositionofthevalve;
A separate limit switchis recommended foreach
ofopenandcloseindication.
SolenoidValve
SOV Weather-proof
SOV-FExplosion-proof
Connectingpipe
thread:
Workingpressure:
Orificediameter:
Electricsource:
Rc1/4
0〜0.97MPa
6mm
100V/50Hz100V60Hz
110V/60Hz200V50Hz
200V60HZ220V/60Hz
Flowswitchingoverairflowbyelectricsignal
4-waysolenoidvalvesfordouble-actionactuators,
4-waysolenoidvaluesforspring-returnactuators,
with one OUT port plugged, or 3-way solenoid
valvesused.
AirFilter-Regulator
F+R
(Completewithpressuregauge)
Connectingpipe
thread:
Workingpressure:
Rc1/4,1/2
Max.inletpressure;
0.97MPa
Max.outletpressure;
0.04MPa〜0.83MPa
(8〜120psi)
For removing moisture, water and other foreign
objects form operating air and for regulating air
pressureatadesirelevel.
SpeedController
SP
Connectingpipe
thread:
Operationpressure:
Rc1/8,1/4,1/2
0.97MPamax.
Forreducingactuatoroperatingspeeds.
QuickExhaustValve
QE
Connectingpipe
thread:
Workingpressure:
Rc1/4,1/2
0.97MPamax
For increasing actuator operation speeds; With
spring-returnactuators,speedincreaseispossible
only in spring-return direction.(Usable only for
actuatorswithoutpositioners.)
ValvePositioner
P
(Completewithpressuregauge)
Connectingpipe
thread:
Supplypressure:
Signalpressure:
SignalCurrent
Airconsumption:
Rc1/4
(pressuregauge:Rc1/8)
0.3˜0.7MPa(43˜100psi)
0.02˜0.1MPa(3˜15psi)
4˜20mA
20Nl/min.max.
(atsupplypressure
0.5MPa)
For operating actuators at any desired position,
with the flow rate controlled by a valve: Valve
positionermaybemountedonbothdouble-action
and spring-return actuator. With use of valve
positioners, flow rate may be stably controlled.
Both air-to-open and air-to-close actuation
modescanbeobtainedbysimplyreversingair.
Silencer
K
Connectingpipe
thread:
Workingpressure:
Rc1/8,1/4,1/2
0.90MPamax.
Forreducingairexhaustnoiseinsolenoidvalve:To
beinstalledintheexhaustportofasolenoidvalve.
AirFilter
F
Connectingpipe
thread:
Workingpressure:
Rc1/4,1/2
0.97MPamax.
For removing moisture, water and other foreign
objectsfromoperatingair.
Lubricator
L
Connectingpipe
thread:
Workingpressure:
Recommendedoil:
Rc1/4,1/2
0.97MPamax.
TurbineoilISOVG32
equivalent
Although KITZ B Series actuators and their
standardsolenoidvalvesaredesignedfornoneed
oflubrication,whenothersolenoidvalvesareused,
orwhenactuatorsaresubjectedtohighoperating
frequency for long periods of time, lubrication is
recommended.
PressureEqualizing
Valve
C
Connectingpipe
thread:
Workingpressure:
Rc1/4
1.37MPamax.
Forequalizinginternalairpressuretoatmospheric
pressuretomanuallyoperateactuators.