6.Specifications
Theactuatorreceivesacontrolsignalandcontrolsthevalveoperationinrealtime.Powersupplyiscutoff
whenthevalvehasreacheditsdesignatedposition.
Whenthevalveopenpositionisshiftedduetoanexternalforce,thevalveopenpositioniscorrectedbythe
actuator.
TypeofActuator RDH124-2
Powersupply
24VDC
−
+
10
20
%
Ratedcurrent Duringoperation:1A Whenstopping:0.1A
Ratedtorque 8N・m
Closing/Openingtime
*2
*3
Selectablebetween3to20seconds(per1second)(Default:3seconds)
Inchingmotionfor4secondsorabove
Resolution *2 Selectablebetween10to200(perevery10seconds) (Default:200)
Insulationclass JISClassE (120℃)
Protectionrate IP55
Insulationresistance 500VDC 10MΩ orabove
Insulationstrength 1minutesfor250VACor1secondfor300VACLeakagecurrent:1mAorbelow
Controlinputsignal *1
4 to 20mADC
1 to 5VDC
2 to 10VDC
(Impedance250Ω)
(Impedance10kΩ)
(Impedance10kΩ)
Wiring Terminalconnection8pins
Serviceenvironment
−10to+50℃ RH30to85%
(Indooruseonlywithnodirectsunlight)
Positonindicator
outputsignal
*1
4 to 20mADC
1 to 5VDC
(LoadresistanceMax.500Ω)
(LoadresistanceMin.100kΩ)
Erroroutput Opencorrectoroutput 30VDC100mAorbelow
Manualoperation *4 Operationpanel
Positionindicator LED(4digits)
Resetoperation
Switchesonoperationpanel(OPEN,SHUTorAUTO/MANUAL)
orpoweroff
Acton *2 Selectablebetweendirectactionandreverseaction(Default:Reverseaction)
Operation atsignalinterruption
*2 SelectablefromFullyclosed/Fullyopen/Stop(Default:Fullyclosed)
Operation afterpowerrecovery
Controlstartsfromwherethepowerwascutoff.
*1Refertothenameplateonthevalvebodyforthedesignatedsignalatthetimeofpurchase.
*2Optionsettingisavailablethroughthepaneloperation.See1.2SettingMethod in Ⅳ Operation .
*3See2.1AutomaticOperationinⅳ Operationforinchingmotion.
*4See2.2ManualOperationinⅣOperation..