EasyManua.ls Logo

Kitz RDH Series - Specifications

Default Icon
34 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5/31
DocumentNo.:KE-4051-00
6.Specifications
Theactuatorreceivesacontrolsignalandcontrolsthevalveoperationinrealtime.Powersupplyiscutoff
whenthevalvehasreacheditsdesignatedposition.
Whenthevalveopenpositionisshiftedduetoanexternalforce,thevalveopenpositioniscorrectedbythe
actuator.
TypeofActuator RDH124-2
Powersupply
24VDC
−
+
10
20
%
Ratedcurrent Duringoperation:1A Whenstopping:0.1A
Ratedtorque 8N・m
Closing/Openingtime
*2
*3
Selectablebetween3to20seconds(per1second)(Default:3seconds)
Inchingmotionfor4secondsorabove
Resolution *2 Selectablebetween10to200(perevery10seconds) (Default:200)
Insulationclass JISClassE (120℃)
Protectionrate IP55
Insulationresistance 500VDC 10MΩ orabove
Insulationstrength 1minutesfor250VACor1secondfor300VACLeakagecurrent:1mAorbelow
Controlinputsignal *1
4 to 20mADC
1 to 5VDC
2 to 10VDC
(Impedance250Ω)
(Impedance10kΩ)
(Impedance10kΩ)
Wiring Terminalconnection8pins
Serviceenvironment
−10to+50℃ RH30to85%
(Indooruseonlywithnodirectsunlight)
Positonindicator
outputsignal
*1
4 to 20mADC
1 to 5VDC
(LoadresistanceMax.500Ω)
(LoadresistanceMin.100kΩ)
Erroroutput Opencorrectoroutput 30VDC100mAorbelow
Manualoperation *4 Operationpanel
Positionindicator LED(4digits)
Resetoperation
Switchesonoperationpanel(OPEN,SHUTorAUTO/MANUAL)
orpoweroff
Acton *2 Selectablebetweendirectactionandreverseaction(Default:Reverseaction)
Operation atsignalinterruption
*2 SelectablefromFullyclosed/Fullyopen/Stop(Default:Fullyclosed)
Operation afterpowerrecovery
Controlstartsfromwherethepowerwascutoff.
*1Refertothenameplateonthevalvebodyforthedesignatedsignalatthetimeofpurchase.
*2Optionsettingisavailablethroughthepaneloperation.See1.2SettingMethod in Ⅳ Operation .
*3See2.1AutomaticOperationinⅳ Operationforinchingmotion.
*4See2.2ManualOperationinⅣOperation..
Kitz RDH Series - Specifications