3.ProtectiveFunction
Thisproductincorporatesvarious protectivefunctions whichstoptheoperationandoutputerror signalsto
protecttheactuatorandthevalve. Ifanyabnormalityisfound,removethecauseimmediatelyandperform
theresetoperationasfollows.
(1)Resetoperation
PresstheOPEN,SHUTandAUTO/MANUALswitchessimultaneouslyforatleast5secondstorestorethe
operation tothe normal state. Reset operationcan be alsoperformed by cutting the powersupply to the
actuatorfor2secondsorlonger.
(2)Protectionofmotoragainstburnoutduetotheconstraintofvalvecausedbyforeignobjects
Ifthevalvedoesnotreachthetargetpositionevenafter1.5timesthesettimeafterinputtingthecommand,
thepowersupplytothemotoriscutoffandtheerrorlampisturnedon.
(3)Protectionofmotoragainstovercurrent
Currentlimitingcircuitisincorporatedtoprotectthemotorfromburning.
(4)Protectionagainstreverseconnectionofpowersupply
Protectivecircuitforreverseconnectionofpowersupplyisincorporated.
(4)Protectionagainstlightningsurge
Surgeabsorberisincorporatedtoprotecttheproductfromamomentaryovervoltagesuchasswitchingsurge
inthepowerlineandinductionlightningsurge.