4. Transport
The cooler shall be transported in an upright condition, without
water filling, on a pallet. In-house handling shall be performed by
means of fork lift trucks or platform lift trucks or crane.
To prevent any distortions of the lower frame, the cooler must
be lowered onto a level surface.
4.1 Transport - Crane
For the transport of the cooler with a crane, screw bore holes
are provided in the lower frame enabling a 2- or 4-point sling
load arrangement to be established.
Use spreader!
To avoid damages of the frame use spreader acc. DIN 15401
and sling band acc. DIN EN 1492-1!
Load Suspension Devices
Lifting rope assemblies acc. DIN 3088 or lifting chain
assemblies acc. DIN 5687/5688 fulfil the requirement of a sling
with equal rope or chain length.
Rope Inclination Angle
Do not exceed a 45° rope inclination angle from the
perpendicular.
Lifting speed
Keep the lifting speed to a minimum (v lift < 10 m/min,
precision lifting, jerk-free lifting)
4.1 Transport specification
- Weight (see Section, 3. Technical data)
- General dimensions (see Technical data)
- Ambient temperature –20°C to +70°C
At ambient temperatures <0°C, it is necessary to completely
drain the water circuits, pumps, water filters and tanks via
draining hoses.
(see also Section 8.2 - Placing out of service).
5. Storage
The cooler shall be stored on a smooth and horizontal surface
having the load-bearing capacity required.
The admissible storage temperature is –20°C to +70°C
provided that all water circuits, pumps, water filters and tanks
are completely drained.
(see section 8.2 - Placing out of service).