EasyManuals Logo

KLH SC 2 User Manual

Default Icon
31 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
KLH Kältetechnik GmbH
u n i v e r s a l c h i l l e r s
ENGLISH
- 20 /31- 14.12.2011 / 01.00
10. Maintenance
M A I N T E N A N C E I N T E R V A L S
Maintenance position
Interval
Activities
General
3 month
Visual inspection (see also chapter 10.1)
Check refrigeration unit for contamination, stains
of water and oil.
Water cycle
Water filter (option)
to be prescribed by the user
clean water filter
Water filling level
2 month
Inspection of the water is limited to water filling
level. degree of water contamination and quality
of water.
If there is an excessive contamination in the tank,
the latter must be cleaned. In case of
longstanding operation, a water treatment is
recommended.
The water treatment by the customer has to
insure, that depositing and corrosion is
avoided under extreme conditions, too.
Please note Security advice (see also chapter 1.3)
According to DIN EN 378 every refrigeration plant must be subjected to
preventive maintenance at least once a year.
A visual inspection of the cooling device is to be performed at regular
intervals.
10 Maintenance