TP-6803 12/1124 Section 1 Installation
tp6809
1. Engine start leads 3 and 4. See the ATS manual for cable size specifications.
Generator Set
ATS
Models RDT
or RSB
1
1
A
B
COM
PWR
3
4
TB1
Generator Set Terminal Block TB1.
See Figure 1-6 for location. Check the
decal on the generator set for terminal block
connections.
Figure 1-20 Engine Start Connections with Transfer Switch Models RDT or RSB
1.8.6 Syst em Connections with
Accessory Modules
See Figure 1-22 through Figure 1-26 for connection
options with up to three accessory modules. Accessory
modules can include one Model RXT transfer switch,
one programmable interface module (PIM), and/or one
load control module (LCM).
See Figure 1-21 for the maximum total cable length with
1, 2, or 3 accessory modules per cable run.
D Use Belden #9402 (4-conductor) or equivalent 20
AWG shielded, twisted-pair cable. Note the shield
connections shown in Figure 1-22.
D Belden #8723 (2-conductor) shielded twisted-pair
cable can be used for connections A and B, and
#12--14 AWG wire can be used for the COM and PWR
connections. The maximum total cable length is the
value shown for #12 or #14 AWG wire in Figure 1-21.
Cable (TB1--PWR and COM)
Maximum length per run, meters (ft.)
Number of Modules (ATS, PIM, and LCM) per Run
1 Module 2 Modules 3 Modules
Belden #9402 or equivalent 20AWG
61 (200) 31 (100) 21 (67)
14 AWG
152 (500) 152 (500) 122 (400)
12 AWG
152 (500) 152 (500) 152 (500)
Figure 1-21 Total Cable Lengths with Accessory Modules Connected in Series (daisy-chain)