TP-6803 12/11 25Section 1 Installation
PIM
LCM
Generator Set
Generator Set Terminal Block TB1.
See Figure 1-6 for location. Check the
decal on the generator set for terminal block
connections.
COM
COM
PWR
COM
PWR
PWR
B
A
B
A
B
A
COM
PWR
B
A
Connect one end of each cable shield
to GROUND at the generator set.
Leave one end of each cable shield
disconnected at the last device.
RXT
1
COM
PWR
B
A
COM
PWR
B
A
Connect shields together
as shown.
1. Communication cable Belden #9402 or equivalent 20 AWG shielded, twisted-pair cable
GND
Note: See Figure 1-21 for maximum total cable length
per run (1 run shown).
A
B
COM
PWR
3
4
TB1
RBUS
12 VDC
Figure 1-22 Accessory Module Communication Connection Details