TP-6803 12/1126 Section 1 Installation
1. Belden #9402 or equivalent, 20 AWG shielded cable with 2 twisted pairs
tp6809
PIM
LCM
RXT ATS
Generator Set
NOTES:
D See Figure 1-6 for terminal block location on generator set. Check
the decal on the generator set for terminal block connections.
D See Figure 1-21 for maximum total cable length per run (3 runs
with 1 module each shown).
D See Figure 1-22 for communication connection detail (A and B,
PWR and COM).
D Use splices or wire nuts to collect multiple leads for connection to
the generator set terminal block. See Figure 1-24.
TB1
1
1
1
Figure 1-23 Accessory Module Connections (three cable runs with one module each)
1
tp6809
1. Splice
Generator Set
Generator Set Terminal Block TB1.
See Figure 1-6 for location. Check the decal on
the generator set for terminal block connections.
COM
PWR
B
A
Connect all of the shield leads on this
end to GROUND at the generator set.
COM
PWR
B
A
TO GROUND
9402 CABLE
9402 CABLE
A
B
COM
PWR
3
4
TB1
RBUS
12 VDC
Figure 1-24 Multiple Connections to the Generator Set