TP-6803 12/1128 Section 1 Installation
tp6809
1. Belden #9402 or equivalent, 20 AWG shielded cable (use one pair); or Belden 8723 or equivalent 20 AWG shielded cable
2. 12--14 AWG wire
PIM
LCM
RXT ATS
1
1
1
Generator Set
AandB
PWR
COM
2
2
2
2
2
2
AandB
AandB
AandB
PWR
COM
PWR
COM
PWR
COM
NOTES:
D See Figure 1-6 for terminal block location on generator set. Check the
decal on the generator set for terminal block connections.
D See Figure 1-21 for maximumtotal cable length with 12 or 14 AWGwire.
(1 run with 3 modules shown).
D See Figure 1-22 for communication connection (A and B) detail.
Connect the cable shield to ground at the generator set.
Figure 1-26 Accessory Module Connections with 12--14 AWG Power Leads (one cable run with three modules
shown)