162 TP-6694 6/22
Description
Controller
Display
Message
Write
Access
Display
SiteTech
GenSet
Mode
Always
Running
Stopped
Range
Setting
Default
Selection
Time
Delay
Range
(sec.)
Default
Time
Delay
(sec.)
Programmer-
Defined
Settings
Low coolant level *
Coolant Lvl Low
Shutdwn
Fixed
5
Not adjustable
Low coolant
temperature
Coolant Temp
Low Warning
Fixed
16°C
(60°F)
0-10
(0-30
inhibit)
5 (0
inhibit)
Low cranking voltage
Lo Crank Vlt
Warning
Fixed
60%
Fixed
6
Not adjustable
Low engine oil level *
Oil Level Low
Warning
Not adjustable
Low engine oil level *
Oil Level Low
Shutdwn
Not adjustable
Low fuel level (diesel
models) *
Fuel Level Low
Warning
0-100%
35%
0-10
10
Low fuel level (diesel
models) *
Fuel Level Low
Shutdwn
0-100%
5%
0-10
0
Low fuel pressure (gas
models) *
Fuel Press Low
Warning
Not adjustable
Low oil pressure
Oil Press Low
Warning
Fixed
(Fixed
inhibit)
5 (5
inhibit)
Not adjustable
Low oil pressure
Oil Press Low
Shutdwn
Fixed
(Fixed
inhibit)
5 (5
inhibit)
Not adjustable
No coolant temperature
signal
Temp Sig Loss
Shutdwn
Not adjustable
No oil pressure signal
Press Sig Loss
Shutdwn
Fixed
5
Not adjustable
Overcrank
Over Crank
Shutdwn
Fixed
(30
inhibit)
Not adjustable
Speed sensor fault
Spd Sens Flt
Warning
Not adjustable
General Functions
Alarm silence,
0-Auto only (NFPA
110), 1-Always
Alarm Silence
Mode
S
A
0-1
1
Aux. inputs 0-5 VDC,
1 analog
Aux Input
Warning
0-100%
100%
0-10
0
Aux. inputs 0-5 VDC, 1
analog
Aux Input
Shutdown
0-100%
100%
0-10
0
Auxiliary inputs, up to 3
digital (2 additional
digital inputs available
with I/O module option)
Aux Input
Warning
0-10
(0-30
inhibit)
0 (0
inhibit)
Auxiliary inputs, up to 3
digital (2 additional
digital inputs available
with I/O module option)
Aux Input
Shutdown
0-10
(0-30
inhibit)
0 (0
inhibit)
Backup parameters
loaded
Backup Pars
Status
Not adjustable
Battery charger 1
communication loss
Bat1CommLoss
Not adjustable
Battery charger 2
communication loss
Bat2CommLoss
Not adjustable
Battery charger fault *
(* does not apply to
charger GM87448)
Batt Chg Flt
Warning
Not adjustable
Battery charger identity
conflict
BatIdErr
Not adjustable
Battery charger
parameter mismatch
ParMisatch
Not adjustable