TP-6694 6/22 163
Description
Controller
Display
Message
Write
Access
Display
SiteTech
GenSet
Mode
Always
Running
Stopped
Range
Setting
Default
Selection
Time
Delay
Range
(sec.)
Default
Time
Delay
(sec.)
Programmer-
Defined
Settings
Battery fault
Battery Flt
Not adjustable
Chicago code active
Chicago Code
Active
Common fault
Common Fault
Shutdwn
Not adjustable
Common warning
Common
Warng
Not adjustable
Contrast (see GenSet
System menu)
Contrast
Display
D
A
1-10
5
Default parameters
loaded
Default Pars
Warning
Not adjustable
Emergency stop
Emerg Stop
Shutdwn
Not adjustable
Enclosure temperature:
high shutdown
Enclsr Temp:
High Shutdwn
S
R
Fixed
Active
Fixed
5 (20
inhibit)
Not adjustable
Engine cooldown
(delay) active
Eng Cooldown
Notice
Not adjustable
Engine start delay
active
Start Delay
Notice
Not adjustable
Engine started
Engine Start
Status
Not adjustable
Engine stopped
Engine Stop
Status
Not adjustable
EPS supplying load
Emerg Pwr On
Notice
Not adjustable
File system error
(controller fault)
File Error
Shutdwn
Not adjustable
Generator running
Gen Running
Notice
Not adjustable
Input/output (optional
module board)
communication loss
OB1 Com Loss
Not adjustable
Internal failure
Intern Error
Shutdwn
Not adjustable
Measurement Units,
0-English, 1-Metric
Measurement
Display
DS
A
0-1
1
Metering
communication loss
MeterCommLos
Shutdwn
Not adjustable
NFPA 110 alarm active
NFPA Alarm
Notice
Not in auto (master
control buttons)
Not In Auto
Warning
Not adjustable
Prime power
application,
0-Standby, 1-Prime
Power Type
DS
A
0-1
0
Remote start
Remote Start
Status
Not adjustable
System ready
System Ready
Status
Not adjustable
System timer failed
Timer Error
Notice
Not adjustable
Generator Functions
AC sensing loss
AC Sens Loss
Warning
Not adjustable
AC sensing loss
AC Sens Loss
Shutdwn
Fixed
3
Not adjustable
Alternator protection
Alt Protect
Shutdwn
Not adjustable