EasyManuals Logo

Kohler 25CCL User Manual

Kohler 25CCL
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #51 background imageLoading...
Page #51 background image
TP-6694 6/22 51
Overvoltage (Each Phase). The fault lamp illuminates red, the alarm horn sounds, and the unit shuts down when the voltage
exceeds the overvoltage setting for the preset time delay period. The local display shows Volts (L1- L2, L2- L3, or L3- L1) High
Shutdwn. See Figure 142 for overvoltage specifications.
Note:
Overvoltage can damage sensitive equipment in less than one second. Install separate overvoltage protection on online
equipment requiring faster than 2-second shutdown.
Overvoltage Setting Range
Time Delay
Overvoltage Default Setting
105%- 135% of nominal
2- 10 sec.
120% at 2 sec.
Figure 14 Overvoltage Specs
Run Relay Overload. The fault lamp illuminates red, the alarm horn sounds, and the unit shuts down when the controller smart
switch that operates generator set wire number 70 (Run) is overloaded. The local display shows Run Relay Overload.
Underfrequency. The fault lamp illuminates red, the alarm horn sounds, and the unit shuts down when the frequency drops
below the underfrequency setting. The local display shows Frequency Low Shutdwn. See Figure 15 for underfrequency
specifications.
Underfreq. Setting Range
Time Delay
Underfrequency Default Setting
80%- 95% of nominal
10 sec. (short term)
90% of nominal
Figure 15 Underfrequency Specs
Note:
The long-term shutdown occurs if the frequency is 1 Hz or more below the system frequency for 60 sec. The long-term shutdown
is not adjustable.
Undervoltage. The fault lamp illuminates red, the alarm horn sounds, and the unit shuts down when the voltage drops below
the undervoltage setting for the time delay period. The local display shows Volts (L1- L2, L2- L3, or L3- L1) Low Shutdwn. See
Figure 16 for undervoltage specifications
Undervoltage Setting Range
Time Delay Range
Undervoltage Default Setting
70%- 95% of nominal
5- 30 sec.
80% of nominal at 10 sec.
Figure 16 Undervoltage Specs
(Voltage) Regulator Communications Loss. The fault lamp illuminates red, the alarm horn sounds, and the unit shuts down
when the voltage regulator to controller communication link is disrupted. The local display shows RegCommLos Shutdwn.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler 25CCL and is the answer not in the manual?

Kohler 25CCL Specifications

General IconGeneral
BrandKohler
Model25CCL
CategoryPortable Generator
LanguageEnglish

Related product manuals