92 TP-6694 6/22
For KG80–KG125, KG80R–KG125R (Kohler Engines KG6208TSD and KG6208THD), use the following:
See Figure 39 and Figure 40.
Natural Gas Operation
Disconnect the black fuel connector (J7).
Disconnect 49 and N17.
Connect the white fuel connector (J8).
For UL applications, connect the optional UL fuel blocking valve (J30).
LPG Vapor Operation
Disconnect the white fuel connector (J8).
Connect the black fuel connector (J7).
Connect 49 and N17.
For UL applications, connect the optional UL fuel blocking valve (J30).
Auto Changeover Natural Gas/LPG Vapor Operation
Connect the white fuel connector (P8 to J8)
Connect the black fuel connectors together in series (P7 to J7, P7A to J7A).
Connect 49 to 49B (QCON10).
Connect 49B to LFP3, Normally Open terminal.
Connect LP1 to LFP3, Common Terminal.
Connect 49A to LFP2, Normally Closed terminal.
Connect N17 to N17B (QCON9).
Connect N17B and N17A to LFP2 Common terminal.
Connect the UL fuel blocking valve (J30).