TP-6081 4/00 7Section 3 Scheduled Maintenance
Service Schedule, continued
Perform Service at Intervals Indicated (X)
Reference
Section
Before
Starting
After
50 Hrs
or
1 Month
Every
100 Hrs
or
3Months
Every
300 Hrs
or
Yearly
ELECTRICAL SYSTEM
Keep the battery charged and in good condition [ 3.9 X
Check and tighten the electrical connections X
Clean the battery cables *
X
(200 hrs)
Check the starter drive and have it serviced if necessary * X
ENGINE AND MOUNTING
Check for fuel and oil leakage *] X
Retighten all nuts and bolts X
Check the mounting bolts/vibromounts and tighten as
necessary
X
(200 hrs)
Check and adjust the valve clearance when the engine is cold* X
Clean the combustion chamber * X
GENERATOR
Test run the generator set 2.3
X
(weekly)
Blow dust out of the generator * 3.1 X
COMPARTMENT
Remove debris from the compartment 2.1 X
* Consult your local distributor/dealer for service
[ Consult the battery manufacturer’s instructions
] Read the WARNING found at the beginning of this manual regarding moving parts