TP-6081 4/006 Section 3 Scheduled Maintenance
3.2 Service Schedule
Perform Service at Intervals Indicated (X)
Reference
Section
Before
Starting
After
50 Hrs
or
1 Month
Every
100 Hrs
or
3Months
Every
300 Hrs
or
Yearly
FUEL SYSTEM
Check the fuel level and fill as necessary 2.1 X
Check the choke operation X
Lubricate the carburetor and choke linkage 3.4.2
X
(200 hrs)
Check the fuel lines and replace them as necessary * X
LUBRICATION SYSTEM
Check the crankcase oil level and add oil as necessary 3.3.2 X
Replace the oil in the crankcase 3.3.4
X
(20 hrs
break-in
period)
X
COOLING SYSTEM
Check the air intake and cooling areas for obstructions and
clean as necessary
X
(Check)
X
(Clean)
IGNITION SYSTEM
Check the spark plug condition, adjust gap, and clean.
Replace if necessary
3.8 X
INTAKE/EXHAUST SYSTEM
Inspect the exhaust system components * 3.6 X
Check the air cleaner for dirty, loose, or damaged parts X
Check the exhaust gas color 3.6
X
(during
operation)
Clean the air cleaner’s paper element 3.5 X
Replace the air cleaner’s paper element 3.5 X
Check the crankcase breather pipe for obstructions * X
Inspect the complete exhaust system * X
Clean the muffler screen/spark arrestor and clean or replace
as necessary
X
* Consult your local distributor/dealer for service