EasyManua.ls Logo

Kohler 6VSG

Kohler 6VSG
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18 Section 1 Installation TP-6842 7/15
1.8.6 PIM Input and Output Connections
The optional programmable interface module (PIM)
provides two programmable inputs and six dry contact
outputs, four of which are programmable. See
TT-1584 for PIM installation and connection
instructions.
Figure 1-13
Figure 1-13 Optional PIM
The default settings for the inputs and outputs are
shown in Figure 1-14. To change the input and output
settings, use a personal computer running Kohler
®
SiteTech
software. See TP-6701, SiteTech Software
Operation Manual, for instructions.
A personal computer running Kohler OnCue
®
software
can be used to actively control PIM outputs. See the
OnCue
®
Software Operation Manual for instructions.
Figure 1-14
Figure 1-14 PIM Factory Default Inputs and Outputs
1.8.7 Communications Kit Output
Connections
The communications kit includes an interface board,
which is factory-installed inside the generator set
enclosure. The inputs and outputs are factory-set to
the settings shown in Figure 1-15.
The outputs are factory-wired from the circuit board to
terminal blocks in the customer connection area. Do
not attempt to connect directly to the interface board.
The output contacts are normally open (NO); outputs
close on activation. Connect customer equipment to
the outputs at the terminal blocks as shown in
Figure 1-15.
Figure 1-15
Figure 1-15 Communications Kit Factory Default
Inputs and Outputs
Figure 1-16
Figure 1-16 Communications Kit Output Connections
Connection PIM Settings
Input 1 None
Input 2 None
Output 1 (Relay 1) Run
Output 2 (Relay 2) Common Fault
Output 3 (Relay 3) Low Battery Voltage
(Programmable)
Output 4 (Relay 4) Not in Auto (Programmable)
Output 5 (Relay 5) Cooldown (Programmable)
Output 6 (Relay 6) Normal Source Failure
(Programmable)
2
1
3
1
1
KPS_040
Connection Communications Kit
Input 1 Fuel Pressure
Input 2 Enclosure Intrusion Alarm
Output 1 (Relay 1) Run
Output 2 (Relay 2) Common Fault
Output 3 (Relay 3) Battery Voltage
Output 4 (Relay 4) Fuel Pressure Low Warning
Output 5 (Relay 5) Enclosure Intrusion Alarm Warning
Output 6 (Relay 6) Reserve Oil Empty (oil makeup kit
required)
commConn
GM85956B

Other manuals for Kohler 6VSG

Related product manuals