TP-6833 2/16 11Section 2 Installation
Section 2 Installation
2.1 Introduction
Kohlerr transfer switches are shipped factory-wired,
factory-tested, and ready for installation. Have the
equipment installed only by trained and qualified
personnel, and verify that the installation complies with
applicable codes and standards. Switch installation
includes the following steps:
D Unpack and inspect the transfer switch upon receipt.
D Verify that the transfer switch voltage and frequency
ratings match the voltages and frequencies of the
sources.
D Install the transfer switch.
D Check the manual operation.
D Connect the controller harness and ground lead.
D Connect the generator set engine start leads.
D Connect the normal power source (utility),
emergency power source (generator set), and load
circuits.
D Connect accessories, if provided.
D Check voltages and operation.
Protect the switch against damage before and during
installation.
Note: A protective device such as a molded-case circuit
breaker or fused disconnect switch MUST be
installed on both sources of incoming power for
circuit protection and used as a disconnect
device.
The functional tests in Section 5 a re a necessary part of
the installation. Be sure to perform the functional tests,
which include voltage checks and operation tests,
before putting the transfer switch into service.
2.2 Receipt of Unit
2.2.1 In sp ection
At the time of delivery, inspect the packaging and the
transfer switch for signs of shipping damage. Unpack
the transfer switch as soon as possible and inspect the
exterior and interior for shipping damage. If damage
and/or rough handling is evident, immediately file a
damage claim with the transportation company.
2.2.2 Liftin g
Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Use adequate lifting capacity.
Never leave the transfer switch
standing upright unless it is securely
bolted in place or stabilized.
WARNING
Refer to Figure 2-1 for the approximate weight of the
transfer switch in a Type 1 enclosure. For other
enclosures, refer to the dimension drawing. Use a
spreader bar to lift the transfer switch. Attach the bar
only to the enclosure’s mounting holes or lifting
brackets; do not lift the unit any other way. Close and
latch the enclosure door before moving the unit.
Amps
Weight kg (lb.)
2-Pole 3-Pole 4-Pole
Model KCS
30--200 28 (62) 30 (65) 31 (68)
230 52 (115) 56 (123) 59 (131)
260--600 179 (395) 183 (403) 188 (414)
800--1000 220 (485) 231 (510) 238 (525)
1200 356 (785) 379 (835)
1600--2000 472 (1040) 494 (1090)
2600--3000 649 (1430) 679 (1495)
4000 975 (2149) 1056 (2328)
Models KCP and KCC
150--600 179 (395) 183 (403) 188 (414)
800--1000 220 (485) 231 (510) 238 (525)
1200 463 (1020) 485 (1070)
1600--2000 533 (1175) 556 (1225)
2600--3000 735 (1620) 765 (1685)
4000 975 (2149) 1056 (2328)
Figure 2-1 Approximate Weights, Type 1 Enclosures