BATTERY
Battery setting page
Battery Warning Voltage:
HIGH: High battery warning voltage. The setting range is 14.0V ~ 15.0V. 14.4V is default setting.
LOW: Low battery warning voltage. The setting range is 10.1V ~ 14.0V. 11.4V is default setting.
This parameter setting is related to “Shutdown Voltage” setting. This setting value should be
higher than “Shutdown Voltage” setting.
Shutdown Voltage: If battery voltage is lower than this point in battery mode, UPS will automatically
shut down. The setting range is 10.0V ~ 12.0V. 10.7V is default setting.
Battery Age: Life expectancy of the battery installed; this setting will produce an Alarm (38 BATT
Replace) when the duration has passed from the battery installation date.
Battery Parameter:
Battery AH: setting battery capacity.