S:\Koldwave\Kompac 4-Series IOM
Koldwave 4830 Transport Drive Dallas, Texas 75247
www.koldwave.com
www.mestekparts.com
3
General Information
Kompac Series Air Conditioners and Heat
Pumps are designed for applications where
outside air is not available and spot cooling
is required. The cord connected Koolette,
Kompac and King Kompac is a 7000
(countertop application), 14000, 16000,
23000 or 26,000 Btu/Hr floor mount
configuration unit to meet any space
requirements.
Our Kompac units are completely self-
contained with the entire refrigeration
system, fan blower assembly, water valve,
and electrical components housed in a metal
cabinet with stainless steel finish. Each unit
will also come along with an optional
remote control. Only power and condenser
water supply, water discharge, and
condensate drain piping are required for
installation. With the heat pump option,
user can manually select HEAT or COOL
options through the touch pad control panel
or through the remote control, depending
upon thermostat command.
The water-cooled condenser requires only
that amount of water needed to achieve the
desired high and low refrigeration system
pressures. The condenser water flow rate
for any entering water temperature can be
obtained using the graph on page 12. A
refrigeration system head pressure actuated
water-regulating valve regulates condenser
water.
General Requirements
For proper control of the water flow rate
entering the automatic water valve, the
minimum water pressure required for
condenser water supply is 30 PSIG. The
condenser water temperature leaving the
unit should not exceed 110F. Ignoring this
compliance will void the warranty on the
refrigeration system. On heat pump models,
it is not recommended to operate the unit in
the heating cycle when the water inlet
temperature is below 50F. Doing so could
reduce the specified heating capacity and
may cause the freeze control to cycle the
compressor off, resulting in a loss of
heating.
IMPORTANT: The Koldwave Kompac
unit has been designed and engineered to
provide needed cooling within the
performance parameters of this manual.
Following the installation and preventative
maintenance instructions can extend the
length of service you receive.