EasyManua.ls Logo

Kolpak PR - Oil Traps; Drain Lines

Kolpak PR
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
Oil Traps
To ensure proper oil return to the compressor, a P-type oil trap should be installed at the base of each suction riser of
four feet or more.
The suction trap must be the same size as the suction line.
Additional traps are necessary for long vertical risers. Add a trap for each length of pipe (approximately 20 feet) to
insure proper oil return.
Suction lines must slope ¼” per 10 feet toward the compressor.
Install a suction line trap at the evaporator outlet if the suction line rises to a point higher than the connection on the
evaporator.
CAUTION
Failure to properly install oil traps can prevent sufficient oil return to the compressor resulting in premature compressor
failure.
Drain Lines
Evaporator coil drain lines should be pitched a minimum of 1/2” per foot to allow proper drainage and exit the walk-in
as quickly as possible.
Insulate and seal the drain line where it passes through the wall.
Copper drain line is required.
Freezer compartment drain lines must have heat tape wrapped around the copper drain line and must have ¾” thick
insulation tubing.
Do not locate drain line P-traps within the freezer space.
Do not reduce the drain line size.
Locate a drain line P-trap outside of the cooler space.
Any outdoor P-traps exposed to low ambient temperatures should be wrapped with a drain line heater (provide 20
watts of heat per foot of drain line at 0°F, 30 watts per foot at -20°F.
Freezer/cooler combo boxes can have one common drain line. However, there must be a P-trap located between the
freezer evaporator and the cooler evaporator located inside the cooler compartment.
The cooler compartment P-trap should be located between the cooler evaporator and the external drain location.