25
Condensing Unit Troubleshooting
Check electrical circuits and motor
winding for shorts or grounds.
Investigate for possible overloading.
Replace fuse after fault is corrected.
Thermal overloads tripped
Overloads are automatically reset.
Check unit closely when unit comes
Defective contactor or coil
System shut down by safety devices
Determine type and cause of shutdown
and correct
None. Wait until cooling is required.
Liquid line solenoid will not open.
Low pressure switch will not close.
Check motor for open windings or short
circuit.
Check all wire junctions. Tighten all
terminal screws.
Compressor noisy or vibrating
Flooding of refrigerant into crankcase
Check superheat setting of expansion
valve
Non-condensable in system
Recover, evacuate and charge
System overcharged with refrigerant
Discharge shut-off valve partially closed
Check electrical circuit or replace
defective fan motor
Insufficient condenser air supply
Check for cause and correct
Faulty head pressure control
Check head pressure control operation.
Suction shut-off valve partially closed
Insufficient refrigerant in system
Locate and repair leak, recover,
evacuate and recharge
Check for proper refrigerant charge
Reduce load or add additional
equipment
Expansion valve overfeeding
Secure and insulate TXV bulb or if
required adjust superheat.
Locate and repair leak, recover,
evacuate and charge.
Clogged liquid line or suction line filter-
drier
Expansion valve malfunctioning
Check and reset for proper superheat
Condensing temperature too low
Check head pressure control