T E C H N I C A L D A T A S H E E T
=======================================
Cooler
Type: Chilly Max 90
---------------
1. GENERAL DATA
---------------
Refrigerant gas:
R410A
Specifications:
---------------
Nominal ambient air: °C 32
Coolant temperature: °C 10 0 20
Cooling Capacity: W 8600 12600
Min ambient air: °C 10
Max ambient air: °C 42
Min coolant temperature: °C 10
Max coolant temperature: °C 25
Evaporator material: Copper
Temperature control: electronic, direct
Temperature display: digital
Control voltage: 24V AC
Main Power supply: 3/PE/50Hz 400V/+-10%
Total absorbed power: kW max:
7.1
Full load current: A max:
13.1
Safety fuse protection: A 16.00
Paint: RAL
Cabinet structure: stainless steel, not painted
-----------------
2. AIR CONDENSER: air cooled, axial
-----------------
Nominal Air Flow: m³/h 4300.00
Number of fan: Unit 1
Nom Absorbed power: kW
0.71
Starting current: A
1.40
--------------
3. COMPRESSOR: full hermetic (dome)
--------------
Number: Unit 1
Total absorbed power: kW max: 5.33
Full load current: A max:
10.15
----------
4. Heater:
----------
Number: Unit 1
Nominal power of the heater: kW 3.00
Nominal stream of the heater: A 4.40